  • 6000 W
  • رنج ولتاژ ورودی وسیع
  • hot plug
  • قابلیت پارالل
  • ماژولار
  • حجم و وزن کم
  • راندمان بالا
PEC-48125 Technical Specification
Model PEC-48125
Input
Voltage 400 +32/-20% VAC (320VAC - 530VAC) Three phase
Frequency 45~66 Hz
Current 10A @ 400 Vac
Power Factor >0.99 at full load, Current THD < 5% typically at full output power when operated with mains voltage THD < 2%
Efficiency Typically >91% at > 40% output power
Surge Protection ANSI C62.41-1991 category B3 - AC lines (Combination Wave 6kV/3kA; Ring Wave 6kV/500A) IEC 61000-4-5 (Impulse) IEC 61000-4-12 (Ring Wave)
EMI compliance CISPR22 Class B
Inrush Current < 16A peak
Soft Start Time Output current ramp-up time 8 seconds to 100A
Isolation 1500VAC input to chassis for 1 minute; (2200VDC 100% testing on production units);
Output
Voltage Float: Adjustable 48 to 58V , Equalize: Adjustable 50 to 60V ,
Current Limit 10~130 A
Power Limit 6000W
Static Regulation Line: ± 0.05%, Load: ± 0.05%
Dynamic Regulation ± 2% for 10A to 90A to 10A step load change; ± 1% of final value within 4ms of step change; ± 1% for a 25% step change in AC input voltage;
Output Noise < 2mV RMS Psophometrically weighted; < 10mV RMS (10kHz - 100MHz); < 100mV peak to peak (10kHz - 100MHz);
Acoustic Noise <50db
Load Sharing Better than ± 5% active current sharing at full load
Protection Over voltage, Over current, Over temperature
Isolation 1000VAC output to chassis for 1 minute; (1500VDC 100% testing on production units);
Monitoring
Current Normally displayed on alphanumeric LCD display by MCSU. Accuracy ± 0.5% at full load.
Voltage Normally displayed on alphanumeric LCD display by MCSU. Accuracy ± 0.5% at full load.
Mode of operation Normally displayed on alphanumeric LCD display by MCSU.
Alarms
LED Green (AC power on), Red(rectifier fault), Yellow(Alarm)
LCD All alarm states are transmitted to the MiniCSU and displayed on the alphanumeric LCD display
Remote Alarms Important alarms available in free contacts relays connected to MiniCSU
Remote Controls
Mode of operation Equalize, Float or Initial Mode is initiated by a signal from the MiniCSU
External Voltage Control Optically coupled PWM signal used to control rectifier Float and Equalize voltage over a limited range to optimally adjust battery voltage for temperature and voltage drop in DC bus, limit the maximum battery recharging current and achieve active current sharing
Rectifier Inhibit Rectifier can be inhibited by a signal from a remote computer, transmitted via the MiniCSU
Environmental
Cooling Forced air cooling
Temperature operating range -25°C to 70°C
Humidity 0 to 100% RH condensing including dripping water and icing conditions
Mechanical
Dimensions Height 86.2 mm (2 U) , Width 482.6 mm , Depth 473.9 mm
Mass 19Kg